3150 Control Valve

零售价

市场价


重量

Quantity
-
+

库存

隐藏域元素占位

3150 Control Valve

Category:

Flecker Control Valve

  • Product Description

     ■ Features/Benefits

    ● Lead-free brass valve body for superior strength and durability

    ● Continuous service flow rate of 95 GPM with a backwash of 105 GPM

    ● Backwash capability accommodates softener tanks up to 63" and filter up to 42" in diameter

    ● Fully adjustable 3- or 5-cycle control for efficient and reliable water treatment system

    ● Designed for single or multiple tank systems

    ● Environmental protective cover for water resistance, corrosion resistance, and UV stability

    ● Time-tested, hydraulically-balanced piston for service and regeneration

    ● Rugged-built electromechanical timer designed with heavy duty 3/8" wide plastic gears

     

    ■ Options

    ● Filter or softener control valves

    ● Downflow co-current or upflow counter-current regeneration

    ● No hard water bypass piston

    ● Brine cam auxiliary switch

    ● Electromechanical timer auxiliary switch

    ● Hot water

    ● Versatile top or side mount

    ● Electromechanical 7- or 12-day time clock, meter delayed, or meter immediate regeneration

    NXT- Network controller uses on board communication capabilities to link multiple valves (via off-the-shelf CAT3, CAT5, or better cables) for system types 4,5,6,7,9,and 14

    XT- Offers a two-line, 16 character LCD backlit display for easy entering of master and user programing as well as view of diagnostics

    Electromechanical Timer- Simple to adjust and easy to service with quick access to all internal components

     

    VALVE SPECIFICATIONS

    Valve Material

    Lead-free brass

    Inlet/Outlet

    2" NPTF/BSPF

    Cycles

    3 or 5

     

    FLOW RATES (50 PSI INLET) – Valve Alone

    Continuous (15 psi drop)

    95 GPM (21.6 m3/h)

    Peak (25 psi drop)

    124 GPM (28.2 m3/h)

    Cv (flow at 1 psi drop)

    24.8

    Max. Backwash (25 psi drop)

    105 GPM (23.8 m3/h)

     

    REGENERATION

    Downflow/Upflow

    Both

    Adjustable Cycles

    Yes

    Time Available

    Electromechanical: 0-164 min/regeneration

     

    NXT: 0-240 min/cycle

     

    XT: 0-240 min/cycle

     

    METER INFORMATION

    Meter Accuracy

    2" Paddle: 3-150 GPM ±5% (.68- 34 m3/h)

    Meter Capacity Range

    2" Standard: 1,250-21,250 gal (5- 75 m3)

     

    2"Extended: 6,250- 106,250 gal (24- 375 m3)

     

    NXT: 1 - 9,900,000 gal (0- 37,476 m3)

     

    XT: 1,000-9,900,000 gal (3.8-37,476 m3)

     

    DIMENSIONS

    Distributor Pilot

    2.375" 0.D. (63 mm)

    Drain Line

    2" NPTF

    Brine Valve

    1600 or 1650: 1"

    Injector System

    1800

    Injector System

    1600 or 1700

    Mounting Base

    4"- 8 UN

    Height from Top of Tank

    10" (254 mm)

    Riser Tube Diameter

    2" (51 mm)

    Riser Height

    1/4" Below top of tank

     

    TYPICAL APPLICATIONS

    Water Softener

    14- 36" diameter

    Filter

    14-42" diameter

     

    ADDITIONAL INFORMATION

    Electrical Rating

    24/110/220V; 50/60 Hz

    Estimated Shipping Weight

    Time Clock: 39 lbs

     

    Metered Valve: 46 lbs

    Pressure

    Hydrostatic: 300 psi (20 bar)

     

    Working: 20- 125 psi (1.4- 8.5 bar)

    Temperature

    Cold Water Valve: 34 - 110°F (1-43°C)

     

    Hot Water Valve (Filter) : 34 - 180°F (1-82°C)

     

    Hot Water Valve (Softener No Meter) : 34- 150°F (1- 66°C)

     